automatic circuit breaker VA55-41-344710
Production and sale of automatic selective switches VA55-41-344710-20UHL3, VA55-41-334710-20UHL3, VA55-41-374710-20UHL3, VA55-41-354710, VA55-41-844710-20UHL3, VA55-41-341810-20UHL3, VA55-41-331810-20UHL3, VA55-41-371810-20UHL3, VA55-41-351810, VA55-41-841810-20UHL3, VA55-41-341110-20UHL3, VA55-41-331110-20UHL3, VA55-41-371110-20UHL3, VA55-41-841110, VA55-41-351110, VA55-41-344610-20UHL3, VA55-41-334610-20UHL3, VA55-41-374610-20UHL3, VA55-41-354610, VA55-41-844610-20UHL3 for rated currents 1000 A, 800 A, 630 A, 1250 A, 400 A, 250 A 660 V~690 V AC, =440V DC. LLC RPE KHEMZ is the official representative of RPE RIMK LLC. Always available VA 5541, VA55-41, VA55-41, VA55 41, VA5541! RPE KHEMZ LLC will send you VA5541 automatic switches by transport companies of Ukraine. Price in Ukraine for circuit breaker VA 55-41-344710, VA 55-41-334710, VA 55-41-374710, VA 55-41-844710, VA 55-41-341810 , VA 55-41-331810, VA 55-41-371810, VA 55-41-841810, VA 55-41-341110-20UHL3, VA 55-41-331110, VA 55-41-371110, VA 55-41-841110, VA 55-41-344610, VA 55-41-334610, VA 55-41-374610, VA 55-41-844610 1000A, 800A is the best. Short delivery times for the VA 55-41 1000A and 800A 3P automatic circuit breakers. 3 year warranty, price for VA55 41. Export
Technical description: automatic circuit breakers VA 55-41 with code 344710 for rated current up to 1000 A are equipped with a semiconductor or microprocessor release, free contacts 4з+4р, independent release and alarm contact. Automatic switch VA 55-41 2-pole are made for direct and alternating (Hz 50, 60) currents. Automatic switch BA50-41 (3P) 3-pole, are made for alternating current.
Automatic circuit breakers VA55 41-344710, VA 55 41 334710, VA 55-41-344510 are designed to conduct current in normal mode and protect against overloads of unacceptable duration, short circuits and unacceptable voltage drops, as well as for infrequent, up to 20 times a day, operational shutdowns of electrical circuits with a rated voltage up to 660 V AC, frequency 50 and 60 Hz and up to 440 V DC. AC breakers can also be used for protection and infrequent direct starts of asynchronous motors in utilization category AC-3.
The circuit breakers VA 50-41 can be equipped with an undervoltage release, a shunt release, free contacts and an electromagnetic drive. Automatic are produced in a stationary version - front, rear and combined accession and in a retractable version.
Technical characteristics of switches VA 55-41:
1. Rated current 1250A, 1000A.
2. Number of poles 3; 2.
3. Rated currents of microprocessor (semiconductor) releases 1250 A, 1000 A, 800 A, 630 A, 400 A, 250A.
4. Setting for the initial tripping current in the zone of overload currents, a multiple of the rated current of the release 1.15
5. Settings for the operating current of electromagnetic overcurrent releases 6300A, 7000A, 5000A, 3800A, 2400A.
6. Rated operational breaking capacity, kA: at rated voltage 380V AC 25, at rated voltage 660V AC 19, at rated voltage 440V DC 50.
7. Wear resistance of circuit breakers: total number of VO cycles 3000, number of VO cycles under load 1500.
8. Weight (stationary version for 1000A) - 27.0 kg. no more.